Lightning Protection Solution for

Weather Radar Station

WeatherI. General Instructions for Scheme Preparation

(a) Implementation Standards

1. National Standards

•

Code for Lightning Protection Design of Buildings GB 50057-2010 (2016

Edition)

•

Technical Specification for Lightning Protection of New Generation Weather

Radar Stations (QX/T 2-2016)

•

Technical Specification for Lightning Protection of Radar Stations GB/T

46477-2025

•

Standard for Construction and Quality Acceptance of Lightning Protection

Engineering for Buildings (GB 50601-2010)

•

GB 16895.12-2021 “Electrical Installations in Buildings – Part 5: Selection

and Installation of Electrical Equipment – Section 53: Isolating, Switching and

Controlling Equipment – Chapter 534: Overvoltage Protection Devices”

2. International Standards

•

IEC 62305-1:2010 “Protection against lightning – Part 1: General principles”

•

IEC 62305-3:2010 “Protection against lightning – Part 3: Physical damage to

structures and life hazard”

•

IEC 61312-1:2021 “Protection against lightning electromagnetic impulse –

Part 1: General principles”

•

ITU-T K.27 “Lightning protection for telecommunication installations

located at high altitudes”

(II) Core Features of the Solution

1.

Specifically designed for weather radar stations , it is compatible with

high-precision radar electronic equipment, high wave transmission, low

electromagnetic interference, and high lightning strike risk (highmountain/coastal/open field) operating conditions;

2.

The entire down conductor uses 50mm² imported super-insulated down

conductors , whose insulation performance, weather resistance, and conductivity

meet IEC international standards, eliminating lightning current leakage, ground

potential backflash, and electromagnetic coupling interference;

(III) Scope and Target of Protection

Protection Scope: Weather radar antenna and radome, radar room, power distribution

system, signal transmission system, monitoring system, and auxiliary facilities;

Protection Objectives: To prevent direct lightning strikes, lightning electromagnetic

pulse interference, ground potential backflash, and inadequate lightning current

discharge, ensuring accurate transmission of weather radar data, uninterrupted 24-hour

operation of equipment, and eliminating the risk of electric shock to personnel.

II. Design of Direct Lightning Protection System

(a) Configuration of lightning rod lightning arrestor for direct

lightning strikes

Conventional fixed lightning protection

uses early discharge lightning rods (compliant with IEC 62305-3 and GB/T 46477-2025

standards), with a leader discharge time ≤60μs. The protection range is calculated based

on a rolling sphere radius of 30m (Class I lightning protection). The lightning rod base is

fixed to the load-bearing structure of the radar antenna platform, avoiding the direction

of the radar’s main detection beam and not obstructing the antenna scanning. The rod

body is made of materials that are resistant to strong winds, corrosion, and have low

electromagnetic interference.

Top-mounted lightning arresters can effectively increase the protection radius. Suitable

options include: Yangbo non-lightning arrester, passive electric field surge arrester, and

active ionization arrester.

Fiberglass support rod (main technical parameters)

3.1) Utilizing high-transparency resin-glass fiber composite materials, it possesses

excellent electrical insulation, withstands high-voltage breakdown, exhibits extremely

low dielectric constant and loss, and boasts a wave transmittance exceeding 85%. It

provides virtually no obstruction or reflection of electromagnetic waves from radar, 5G

signals, and meteorological monitoring equipment. This is crucial for locations such as

airport meteorological stations and military radar stations, effectively ensuring data

accuracy.

Although its density is only 1/4 to 1/5 that of steel, its strength is close to or evenexceeds that of ordinary steel, and it is lightweight.

It has excellent corrosion resistance, aging resistance, and weather resistance. In coastal

high salt spray environments, its corrosion resistance is more prominent than other

traditional materials.

Yangbo lightning protection can be set with different colors and heights from 2 meters

to 50 meters according to different application scenarios , with a maximum wind

resistance of level 17 .

3.2) Main technical parameters of fiberglass support rods

Specific

gravity (g/cm3)

1.9-2.1

2.

Tensile strength (MPa)

518

3.

Tensile modulus (GPa):

longitudinal 20, transverse 5.5

4.

Bending strength (MPa) 870

5.

Flexural modulus (GPa)

38

6.

Compressive strength (MPa): Longitudinal 430-450, Transverse 150-170

7. Operating temperature: -50℃ to 60℃

8. Product materials have third-party testing reports and certificates.4. Yangbo Lightning Protection’s Lightning Protection Recommendations for

Special Scenarios : For scenarios where antennas need to rotate over a wide range,

space is limited, and signal obstruction needs to be avoided, we recommend configuring

fiberglass lifting lightning rods . The fiberglass lifting tower is made of high-

transmittance fiberglass composite material with a transmittance of ≥95%, no

electromagnetic reflection, and manual/electric lifting controllable. The top is also

equipped with an early discharge lightning arrester, which combines protection and

radar compatibility.5. Mobile and rapid deployment of lifting lightning protection devices

Yangbo Lightning Protection has focused on lightning protection and disaster reduction

for 20 years. For special scenarios such as airports, military, training scenarios, and

emergency rescue, it has launched integrated lightning protection devices, including

vehicle-mounted mobile lifting towers, equipped with lightning warning, lightning

location, and lightning monitoring.

Each lightning rod down conductor of the radar station’s lightning strike monitoring

device is connected to a Yangbo mechanical lightning counter (no power supply,

maintenance-free) or a Yangbo intelligent lightning current peak monitoring box to

record surge count, polarity, peak value, wavefront time, half-peak time, Q value, energy,

current steepness, and date/time of occurrence in real time. The maximum count is

9999 times , and the data is stored locally and uploaded remotely, meeting the

requirements for lightning protection monitoring and traceability.(II) Design of Super Insulated Down Leads

1.

The down conductor

uses imported 50mm² super-insulated down conductors . The conductor is

oxygen-free pure copper with a conductivity ≥98% IACS. The insulation layer uses

imported weather-resistant super-insulating material with a breakdown voltage ≥15kV,

temperature resistance of -40℃ to 120℃, UV resistance, salt spray resistance, acid and

alkali corrosion resistance, and insulation resistance ≥1000MΩ. It meets the insulation

and conductivity performance requirements of IEC 60245 and GB 50057-2010 for down

conductors.

2.

Layout specifications

Each lightning rod is equipped with ≥2 super-insulated down conductors, which are

symmetrically and vertically arranged along the building structure, with a down

conductor spacing of ≤12m (National Standard Class I Lightning Protection

Requirements).

The down conductor should be run through insulating sleeves or concealed throughout

to avoid exposure, and large-radius elbows should be used at bends to avoid sharp-angle

bends.

The connection between the down conductor and the lightning arrester and grounding

device adopts zero-ohm composite grounding body crimping/hot-melt welding to

ensure zero contact resistance, and the connection parts are treated with double-layer

insulation and sealing.

The distance between the down conductor and radar cables, metal cable trays, and

equipment cabinets shall be ≥1.5m to avoid electromagnetic coupling interference with

radar signals from lightning, and shall comply with the requirements of IEC 61312-1

lightning electromagnetic pulse protection.

Installation requires

a fixed spacing of ≤1.5m for the down conductors. The fasteners should be made of

insulating and corrosion-resistant materials. Direct contact with building metal

structures and equipment metal casings is strictly prohibited. Full insulation and

isolation should be maintained throughout the process to completely prevent

lateral discharge of lightning current and ground potential backflash, thus protecting the

surrounding precision electronic equipment.

III. Design of Intelligent Lightning Protection

Monitoring System

(I) System Composition

It consists of a lightning current peak monitoring box, an online grounding resistance

monitoring box, an intelligent lightning protection host, a remote monitoring platform,and an alarm module, and meets the requirements of QX/T 2-2016 Intelligent

Monitoring Requirements for Meteorological Radar Stations.

(II) Core Monitoring Functions

1.

Online lightning strike monitoring : Lightning current parameters are collected

in real time through the peak monitoring box, and the data is synchronously uploaded to

the intelligent host to generate lightning strike statistical reports;

2.

Online grounding resistance monitoring : The online grounding resistance

monitoring box monitors the grounding grid resistance value in real time, sets a

threshold (≤4Ω), and immediately alarms if the value exceeds the threshold;

3.

Down conductor status monitoring : Real-time monitoring of the conduction

status and insulation performance of the super-insulated down conductor, and

immediate alarm upon detection of damage, breakage, or insulation failure;

4.

Remote intelligent management and control : Supports remote data viewing,

historical traceability, and fault location via computer and mobile phone, and features

multi-level alarms including sound and light, SMS, and telephone, enabling unattended

intelligent operation and maintenance.

(iii) Standard compliance

The system’s data acquisition, transmission, and alarm logic comply with IEC 62305-2

and GB 50057-2010 requirements for lightning protection monitoring and early

warning, and are suitable for the high-reliability operation and maintenance needs of

meteorological radar stations.

IV. Design of a New Long-Term Grounding System

(a) Grounding standard requirements

A shared grounding system is adopted , combining lightning protection grounding,

equipment working grounding, shielding grounding, and power supply grounding. The

grounding resistance is ≤4Ω , and ≤10Ω in areas with high soil resistivity, which meets

the grounding requirements of GB 50057-2010 and IEC 62305-3.

(II) Grounding Materials and Construction

1.

Main grounding material : Stainless steel titanium composite grounding

material is used , with a corrosion resistance life of ≥50 years, stable conductivity, no

electrochemical corrosion, and suitable for harsh geological conditions such as high

mountains, coastal areas, and saline-alkali land;

2.

Node connection : All nodes use zero-ohm composite grounding bodies to

achieve zero contact resistance connection, avoid resistance loss of traditional

connection methods, and improve lightning current discharge efficiency;3.

Resistance reduction device : In high resistivity areas , a hollow ion

grounding device is configured with a built-in long-lasting ion slow-release agent to

continuously improve soil resistivity, with stable resistance reduction effect and no need

for subsequent maintenance.

4.

Grounding grid structure : A closed ring three-dimensional grounding grid is

adopted, which combines horizontal grounding body and vertical grounding electrode,

and is reliably connected at multiple points with 50mm² imported super-insulated down

conductor to form a complete discharge channel.

V. Lightning Electromagnetic Pulse (LEMP) Protection

Design

(a) Shielding and protection

a Faraday cage made of steel mesh and metal shielding plate . The shielding mesh is ≤

600mm×600mm, which complies with the IEC 61312-1 standard. The antenna feeder

and signal cable are double-shielded cables, which are laid through metal shielding

channels throughout, and the shielding layer is grounded at both ends.

(ii) Multi-stage surge protection

Power system: Three-level surge protectors (SPDs) are used for protection. The main

distribution cabinet is equipped with a Class I SPD, the computer room distribution box

is equipped with a Class II SPD, and the radar equipment front end is equipped with a

Class III SPD, which complies with GB 16895.12 and IEC 61643-1 standards.

Signal/Antenna Feeder System: Corresponding antenna feeder SPD and signal SPD are

installed. The insertion loss is low and does not affect the transmission of weather radar

signals.

(iii) Equipotential bonding

The computer room is equipped with an M-type equipotential grounding grid. All

equipment cabinets, anti-static floors, metal cable trays, shielding bodies, and cable

shielding layers are connected to the equipotential grid via the shortest path to

eliminate potential differences and prevent ground potential backflash, in accordance

with the equipotential requirements of GB 50057-2010.

VI. Construction Technical Requirements

1.

Before installing 50mm² imported super-insulated down conductors, the integrity

of the insulation layer and the conductor resistance must be checked, and construction

can only proceed after they pass the inspection.

2.

Twisting or loose connection of the down conductor is strictly prohibited. Hot meltwelding or special crimping parts must be used. The insulation layer must be restored

after connection.

3.

The construction of the grounding device shall be carried out in strict accordance

with GB 50601-2010. The backfill soil shall be free of stones and debris, and shall be

compacted in layers. The resistance reduction area shall be constructed in accordance

with the process requirements.

4.

Wiring of intelligent monitoring equipment should be standardized, and

waterproofing and electromagnetic interference protection should be carried out.

Monitoring accuracy should be calibrated.

5.

Throughout the construction process, protective measures should be taken to

avoid damage to radar equipment, cables, and the insulation layer of the super-insulated

down conductors.

VII. Acceptance Standards

1.

Lightning arrester protection range: Tested and found to fully cover all protected

objects of the radar station, in compliance with the requirements of GB 50057-2010

rolling sphere method;

2.

Down conductor: 50mm² imported super-insulated down conductor with good

conductivity and insulation performance meets the standards. The installation spacing

and fixing method comply with the specifications.

3.

Grounding resistance: The measured grounding resistance is ≤4Ω, meeting both

national and international standards.

4.

Intelligent monitoring system: accurate monitoring data, timely alarm response,

and normal remote transmission;

5.

Surge protection, equipotential bonding, and shielding systems: Compliant with

lightning electromagnetic pulse protection standards, with no risk of electromagnetic

interference.

VIII. Operation and Maintenance Management

Requirements

1.

The status of the super-insulated down conductor, grounding resistance, and

lightning strike count data are checked quarterly through the intelligent lightning

protection system.

2.

The lightning protection system is fully inspected annually, monitoring equipment

is calibrated, and the corrosion of the down conductor insulation and grounding device

is checked.3.

Establish operation and maintenance files to record lightning strike data, test

results, and maintenance content, in accordance with the lightning protection operation

and maintenance specifications for meteorological radar stations;

4.

If any issues are found, such as damaged down conductor insulation, excessive

grounding resistance, or monitoring equipment malfunction, immediate rectification is

required to ensure the continuous effectiveness of the lightning protection system. Radar Stations