YBA1‑25B/3+NPE

 

图片1

 

Product Description

Installed in the main distribution boards of buildings or power inlet where lightning current may enter。

Installed in the main distribution boards of buildings or power inlet where lightning current may enter。

Nominal waveform: 10/350 μs。

Suitable for sites with external lightning protection system and risk of direct lightning current intrusion.

Monoblock Multi-Pole SPD — Class I·Class II · Type 1·Type 2

 

Parameter  Spec 
Location of Use Main Distribution Boards
Network Systems TT, TN-S
Mode of Protection L-N / L-PE, N-PE
Surge Ratings Iimp = 25 kA / 100 kA (10/350μs); In = 25 kA / 100 kA (8/20μs)
IEC/EN Category Class I+II / Type 1+2
Protective Elements High Energy MOV and GDT
Housing Monoblock Design
Compliance IEC 61643-11:2025; EN 61643-11:2025

Technical Data — IEC Electrical

 

Parameter  Spec 
Nominal AC Voltage (50/60Hz) (L-N) 120V / 230V / 385V
Max. Continuous Operating Voltage (L-N) Uc 150V / 275V / 385V
Max. Continuous Operating Voltage (N-PE) Uc 255V
Nominal Discharge Current (L-N)/(N-PE) In 25 kA / 100 kA
Max. Discharge Current (L-N)/(N-PE) Imax 100 kA
Impulse Discharge Current (L-N)/(N-PE) Iimp 25 kA / 100 kA
Total Discharge Current Itotal 100 kA
Specific Energy (L-N)/(N-PE) W/R 156 kJ/Ω / 2.5 MJ/Ω
Charge (L-N)/(N-PE) Q 12.5 As / 50 As
Voltage Protection Level (L-N)/(N-PE) Up 1000/1500V; 1500/1500V; 1600/1500V; 1800/1500V
Follow Current Interrupting Rating Ifi 100 Arms
Response Time (L-N)/(N-PE) tA < 25 ns / < 100 ns
Back-Up Fuse (max) 315 A gL/gG
Short-Circuit Current Rating (L-N) IsccR 50 kA
TOV Withstand 5s (L-N) UT 180V / 335V / 335V
TOV Withstand 120min (L-N) UT 230V / 440V / 440V
TOV Withstand 200ms (N-PE) UT 1200V

Internal setup