YBA1‑12.5B/3+NPE

YBA1‑12.5B/3+NPE

 

图片1

Pluggable Multi-Pole Surge Protective Device

 

Installation Location

Installed in the main distribution boards of buildings or power inlet where lightning current may enter.

 Function Description

It is mainYBA used to withstand lightning current surges.

 Key Parameter

Nominal waveform: 10/350 μs, Impulse Discharge Current Iimp=12.5kA.

Application

Suitable for sites with external lightning protection system and risk of direct lightning current intrusion.

 

Parameter  Spec 
Location of Use Main Distribution Boards
Network Systems TT, TN-S
Mode of Protection N-PE, L-N
Surge Ratings Iimp = 12.5 kA (10/350μs); In = 20 kA (8/20μs)
IEC/EN/UL Category Class I+II / Type 1+2 / Type 1CA
Protective Elements High Energy MOV and GDT
Housing Pluggable Design
Compliance IEC 61643-11:2025; EN 61643-11:2025; UL 1449 4th Edition

Technical Data — IEC Electrical

Parameter  Spec 
Nominal AC Voltage (L-N) Uc 120V / 230V / 380V
Max. Continuous Operating Voltage (L-N) Uc 150V / 275V / 385V
Max. Continuous Operating Voltage (N-PE) Uc 255V
Nominal Discharge Current (L-N)/(N-PE) In 20 kA / 50 kA
Max. Discharge Current (L-N)/(N-PE) Imax 50 kA / 100 kA
Impulse Discharge Current (L-N)/(N-PE) Iimp 12.5 kA / 50 kA
Specific Energy W/R 39 kJΩ / 625 kJΩ
Charge Q 6.25 As / 25 As
Voltage Protection Level (L-N)/(N-PE) Up 1500V
Follow Current Interrupting Rating (N-PE) Ifi 100 Arms
Response Time (L-N)/(N-PE) tA < 25 ns / < 100 ns
Back-Up Fuse (max) 315 A gL/gG
Short-Circuit Current Rating (L-N) IsccR 25 kA / 50 kA
TOV Withstand 5s (L-N) UT 180V / 335V / 335V
TOV 120min Mode (L-N) Safe Fail
TOV Withstand 200ms (N-PE) UT 1200V

Internal Settings

图片4

 

Size and Packaging

图片5

 

Connection diagram

图片6