YBA‑C40/1+NPE
YBA-C40/3+NPE Pluggable Multi-Pole Surge Protective Device
Installation Location
Installed in building sub-distribution boards, secondary distribution circuits or three-phase four-wire power distribution systems.
Function Description
It is mainly used to withstand induced lightning surge currents and provide Class II power lightning protection for downstream three-phase four-wire distribution equipment
Key Parameter
Nominal waveform: 8/20μs, Max. Discharge Current Imax=40kA.
Application
Suitable for three-phase four-wire distribution sites with TT and TN-S systems, and building distribution circuits where induced lightning surge risk exists.
| Parameter | Spec |
|---|---|
| Location of Use | Sub-Distribution Boards |
| Network Systems | TT, TN-S |
| Mode of Protection | L-N, N-PE |
| Surge Ratings | In = 20 kA (8/20μs) |
| IEC/EN/UL Category | Class II / Type 2 / Type 1CA |
| Protective Elements | High Energy MOV and GDT |
| Housing | Pluggable Design |
| Compliance | IEC 61643-11:2025; EN 61643-11:2025; UL 1449 4th Edition |
Technical Data — IEC Electrica
| Parameter | Spec |
|---|---|
| Nominal AC Voltage (L-N) Uc | 120V / 230V / 385V |
| Max. Continuous Operating Voltage (L-N) Uc | 150V / 275V / 385V |
| Max. Continuous Operating Voltage (N-PE) Uc | 255V |
| Nominal Discharge Current (L-N)/(N-PE) In | 20 kA / 20 kA |
| Max. Discharge Current (L-N)/(N-PE) Imax | 40 kA / 40 kA |
| Voltage Protection Level (L-N)/(N-PE) Up | 1000/1000V; 1500/1000V; 1600/1000V; 1750/1000V |
| Follow Current Interrupting Rating (N-PE) Ifi | 100 Arms |
| Response Time (L-N)/(N-PE) tA | < 25 ns / < 100 ns |
| Back-Up Fuse (max) | 125 A gL/gG |
| Short-Circuit Current Rating (L-N) IsccR | 25 kA / 50 kA |
| TOV Withstand 5s (L-N) UT | 180V / 335V / 335V |
| TOV 120min Mode (L-N) | Safe Fail |
| TOV Withstand 200ms (N-PE) UT | 1200V |